Iном пускателя. А | Среднее значение тока теплового реле, А | Пределы регулирования тока срабатывания, А |
10 | 0,14 | 0,1 -0,17 |
0,21 | 0,16-0,26 | |
0,32 | 0,24 - 0,4 | |
0,52 | 0,38 - 0,65 | |
0,8 | 0,61 - 1,0 | |
1,3 | 0,95- 1,6 | |
2,0 | 1,5-2,6 | |
3,2 | 2,4 - 4,0 | |
5,0 | 3,8 - 60 | |
6,8 | 5,5 - 8,0 | |
8,5 | 7,0- 10,0 | |
25 | 8,5 | 7,0 - 10,0 |
12,0 | 9,5 - 14,0 | |
16,0 | 13,0- 19,0 | |
21,5 | 18,0-25,0 | |
40 | 21,5 | 18,0-25,0 |
27,5 | 23,0 - 32,0 | |
35,0 | 30,0 - 40,0 | |
63 | 35,0 | 30,0 - 40,0 |
44,0 | 38,0 - 50,0 | |
52,0 | 47,0 - 57,0 | |
60,0 | 54,0 - 63,0 | |
80 | 60,0 | 54,0 - 63,0 |
71,5 | 63,0 - 80,0 | |
125 | 90,0 | 75,0- 105,0 |
110,0 | 95,0- 125,0 | |
200 | 110,0 | 95,0- 125,0 |
140,0 | 120,0- 160,0 | |
175,0 | 150,0 - 200,0 |